Product Code : MCP-AS
Product Description

Manual Controllers

Protection, Supervision Salient features

  • Voltage monitoring and protection for under/over voltage and over speeding.
  • Low Fuel
  • Charging Alternator Fail/V-Belt
  • Oil Pressure
  • Fan Fault protection( 1Ph model B)
  • HWT
  • Mains supervision Ph- Neutral or Ph-Ph for auto shut off
  • Canopy Temperature/RWL
  • Over Load
  • Emergency


Measurement & Display

MCP-AS equipped with LCD display and displays

  • Generator voltage (Ph-N, Ph-Ph)
  • Radiator Temp in degree centigrade(Model -A)
  • Mains Voltage (Ph-N, Ph-Ph)
  • Generator Frequency
  • Fuel Level
  • Generator Current
  • Programmed settings
  • Fan Current(1 Ph Model B)
  • KW
  • Battery Voltage
  • PF
  • Generator Run Hour
  • KWhr
  • RPM
  • Oil Pressure in KG/cm

Normally the display auto scrolls and displays a set of parameter for 10 seconds, but any time the Next key (^) can be pressed to select the next parameter window.

Parameter Mode:

Display

Explanation of parameter

Factory setting

Setting Range

Generator O/V

Max. permissible voltage, above this the voltage is treated unhealthy & the Generator is stopped.

270V

80-300V

Generator U/V

Min. permissible voltage, below this the voltage is treated unhealthy & the Generator is stopped

180V

80-300V

Gen Sup Delay

The time for which the Generator voltage should, continuously be unhealthy to generate a fault condition.

10Sec.

1-999 Sec.

Mains O/V

Max. permissible voltage, below this the voltage is treated healthy & the Generator is stopped.

270V

80-500V

Mains U/V

Min. permissible voltage, above this the voltage is treated healthy & the Generator is stopped

180V

80-500V

Mains Res Time

The time for which the Generator voltage should, continuously be unhealthy to generate a fault condition.

10Sec

1-999 Sec.

CT Ratio

Available in models having provision for /5 CTs. Not required for Procom Make CTs

1

1-999

Generator O/C*

Max. permissible current, above this the Current is treated unhealthy & the Generator is stopped.

6 (for /5 A CT)
42A (for Procom CT)
1-999 (for /5 A CT)
1-199 A (for Procom CT)

Gen O/C Delay

The time for which the Generator Current should, continuously be unhealthy to generate a fault condition.

5 Sec.

1-999 Sec.

Generator S/C*

Max. permissible current, above this the Current is treated unhealthy & the Generator is stopped.

10 A (for/5A CT)
84A (for Procom CT)
1-999 (for/5 A CT)
1-199 A (for Procom CT)

Gen S/C Delay

The time for which the Generator Current should, continuously be unhealthy to generate a fault condition.

2Sec

1-999 Sec.

Generator O/F*

Over frequency setting

65 Hz

40-80 Hz

Specification

AC voltage withstand

330 VAC (Phase to neutral)

Measurement Accuracy

Voltage & Current

1%

Power & KWh

2%

Surge 1.2/50 Usec

2.5KV

Battery Voltage

Suitable for 12V/24 VDC System

Min. voltage to power on

9V

Min Running Voltage after Power on

4V

Max. Battery Voltage

35V

DC Interruption time

1 Sec.

Digital Output

+ 12V

Cut out Dimensions

92mm X 92mm

Depth

120mm

Digital Input Level which is battery supply

Battery Voltage (Negative) except Charging Alt

 Download PDF File

 


MRM PROCOM PVT. LTD.

Contact Us

( *represents compulsory fields )

Tips on getting accurate quotes. Please include product name, order quantity, usage, special requests if any in your inquiry.



Contact Details
  • MRM PROCOM PVT. LTD.
  • Plot No. 20-21, Sector 59, Phase-2, Faridabad - 121004, Haryana, India
  • Send Inquiry      Call Me Free Offline Send SMS
  • Mr. Pankaj Gupta (Director)
MRM PROCOM PVT. LTD. All Rights Reserved.