AMF Controllers

AMF Controllers
AMF Controllers
Product Code : DGC-7
Product Description

AMF Controllers

Salient features of the DGC-7

Protection & Supervision:

  • 3 phase Under & Over, voltage, frequency and voltage unbalance protection for EB supply (True RMS measurement for Voltage)
  • Phase under & over, voltage and frequency protection of Generator supply (True RMS measurement for voltage)
  • User programmable Cranking attempt.
  • User programmable Crank Time and delay between two successive cranks
  • User programmable load transfer to DG delay.
  • Generator over speed supervision
  • Mains Restoration supervision
  • DC Battery Voltage supervision (Under & Over voltage)
  • External fault detection (5 digital inputs)
  • Two Circuit breaker check back inputs.
  • External engine running signal
  • External signal for remote operation
  • DG Fail to start supervision and indication
  • DG fail to stop supervision and indication
  • Unit remains fully operational even if battery voltage falls to zero volts for one sec.

Measurement & Display

DGC-7, equipped with 16 Segment, 21ine LCD display, displays:

  • EB voltages of RYB phase and frequency
  • Generator voltage and frequency
  • DC battery voltage
  • Run Hour time

Programmed values

The display shows the mains voltage parameters while the mains is healthy and automatically switches over to display the generator parameters while the generator is running.

Setting Table

Parameter Name on First Row of LCD

Explanation of parameter

Factory setting

Setting Range

Mains O/V

Max. Permissible voltage, above this the voltage is treated unhealthy & Generator is started.

270V

80-270V

Mains U/V

Min. permissible voltage, below this the voltage is treated unhealthy & Generator is started

180V

80-270V

Mains Sup Delay

Time for which the mains voltage has to be unhealthy (under or over voltage as defined above in l & 2) before starting the generator.

10Sec

0-999Sec

Mains O/F

Max. permissible mains frequency, above this frequency the mains is treated unhealthy & Generator is started.

55Hz

40-65Hz

Mains U/F

Min. permissible mains frequency, below this frequency the mains is treated unhealthy & Generator is started.

45Hz

40-65Hz

Mains Freq Delay

Time for which the mains frequency  as to be unhealthy (under or over voltage as defined above in 4 & 5) before starting the generator..

10Sec

0-999Sec

Mains Vol Unbal

Max. permissible voltage difference between two phases of mains. Above this the voltage is treated to be unbalanced and generator is started.

40

10-100 Disable

Unbalance Delay

Duration for which unbalance can be tolerated before starting the Generator.

10Sec

0-999Sec

Generator O/V

Max. permissible generator voltage, above this the generator voltage is treated unhealthy & the generator is stopped.
Generator contactor is released and mains contactor is closed. Hooter shall be activated and DG Vol LED shall start flashing.

270V

80-270V

Generator U/V

Min. permissible generator voltage, below this the generator voltage is treated unhealthy & the generator is stopped.
Generator contactor is released and mains contactor is closed. Hooted shall be activated and DG Vol LED shall start flashing.

180V

80-270V

Specifications

AC voltage Withstand

330 VAC continuously (Phase to neutral)

Measurement Accuracy

1%

Surge 1.2/50 Usec

2.5KV

Battery Voltage

Suitable for 12V/24 VDC System

Min. voltage to power on

9V

Min Running Voltage after Power on

5V

Max. Battery Voltage

35V

DC Interruption time

1 Sec.

Contact(MCB)

NC, 230V / 6A

Contact(GCB)

NO, 230V / 6A

Contact(Hooter)

NO, 230V/ 6A

Contact(Fuel)

NO, 230V/ 6A

Contact(Crank)

NO, 230V/ 6A

Contact(Ann 6 Nos)

NO, 230V/ 1A

Cut out Dimensions

186mm X 90mm

Depth

120mm

Digital Input Level

Battery Voltage (Negative)

Operation mode

Auto , Manual, Test & off mode

Feature

Three phase mains/ single phase DG with PFC

Measurement

3 phase mains voltage single phase generator voltage generator Frequency, DC Battery voltage RPM, BTS Voltage, Temperature service due

Protection

External fault input 4 Nos., Over speed, Over & under voltage, over load, Emergency stop, Fail to startFail to stop, chq/V-Belt

Battery supply

7-35 VDC

Housing

DIN Standard 186x96mm

Download PDF File


MRM PROCOM PVT. LTD.

Contact Us

( *represents compulsory fields )

Tips on getting accurate quotes. Please include product name, order quantity, usage, special requests if any in your inquiry.



Contact Details
  • MRM PROCOM PVT. LTD.
  • Plot No. 20-21, Sector 59, Phase-2, Faridabad - 121004, Haryana, India
  • Send Inquiry      Call Me Free Offline Send SMS
  • Mr. Pankaj Gupta (Director)
MRM PROCOM PVT. LTD. All Rights Reserved.