Product Description

AMF Controllers

Protection, Supervision Salient features

  • Mains 3 phase monitoring for under/over voltage, under/over frequency, Overload Phase Sequence and Phase voltages unbalance.
  • Generators 3 phase monitoring and protection for under/over voltage, under/over frequency, over load, under/over frequency and over speeding.
  • DC Battery Voltage supervision (Under & Over voltage)
  • 7 digital input for system protection
  • DG Fail to Start supervision
  • Fuel, HWT and LLOP measurements and value display.
  • DG fail to Stop supervision

Measurement & Display

16 segment 2 line LCD displays the following parameters. Some of the parameters are model dependent and are available in only those models.

  • Mains 3 Phase voltage
  • Generator 3 Phase Voltage
  • Generator Frequency
  • Generator Run Hour
  • Fuel Level, HWT and LLOP
  • KW and PF of generator
  • Fault History
  • Mains Frequency
  • Load 3 Phase current
  • Battery Voltage
  • RPM
  • KWh of generator
  • Service Hour Due
  • Programmed settings

Normally the display auto scrolls and displays a set of parameter for 10 seconds, but any time the Next key (^) can be pressed to select the next parameter window.

Parameter Mode

Parameter name on first row of LCD

Explanation of parameter

Factory Setting

Setting Range

Common to all Models

Mains O/V

Max. Permissible voltage, above this the voltage is treated unhealthy & Generator is started

270V

80-300V

Mains U/V

Min. permissible voltage, below this the voltage is treated unhealthy & Generator is started

180V

80-270V

Mains Sup Delay

Time for which the Mains voltage has to be unhealthy (Under or Over voltage as defined above in 1 & 2) before starting the Generator

10Sec

1-999Sec

Mains O/F

Max. Permissible Mains frequency,above this frequency the Mains is treated unhealthy & Generator is started

55Hz

40-65Hz

Mains U/F

Min. permissible Mains frequency,below this frequency the Mains is

treated unhealthy & Generator is started

45Hz

40-65Hz

Mains Freq Delay

Time for which the Mains frequency has to be unhealthy (under or over voltage as defined above in 4 & 5) before starting the Generator.

10 Sec

1-999 Sec.

Mains Vol Unbal

Max. Permissible voltage difference between two phases of mains. Above this the voltage is treated to be unbalanced and Generator is started.

Disable

10-100 Disable

Mains Ph Seq

Enabled/ Disabled

Off

On/ Off

Phase Seq Delay

Duration for which the unhealthy phase sequence is acceptable. After this time the mains is treated as unhealthy and the engine is started

10 Sec

1-999Sec

Unbalance Delay

Duration for which unbalance can be allowed before starting the Generator. This parameter is not available if (7) is set to disabled.

10Sec

1-999Sec

Gen Start Delay

The starting of generator is delayed by this time after the mains unhealthy timers have expired and the mains contact has been released. This is required in certain applications where immediate generator starting is not required but the mains contactor are to be protected. This timer is automatically reset, if during this duration the mains become healthy for “Mains Restoration Delay” (28)

Disable

1-999

Gen Start Unit

The generator start delay(11) can be programmed in seconds or minutes. This parameter is not available if (11) is disabled.

Sec

Sec-Min

 

Specifications

AC voltage withstand

330 VAC (Phase to neutral)

Measurement Accuracy

Voltages & Current

1% of Measurement

Power & Energies

2%

Surge 1.2/50Usec

2.5KV

Battery Voltage

Suitable for 12V/24 VDC System

Min. voltage to power on

9V

Min Running Voltage after Power on

4V

Max. Battery Voltage

35V

DC Interruption time

1 Sec.

Contact(MCB)

NC, 230V / 6A

Contact(GCB)

NO, 230V / 6A

Contact(Hooter)

NO, 230V / 6A

Contact(Fuel)

NO, 230V / 6A

Contact(Crank)

NO, 230V / 6A

Contact Choke

NO, 230V / 6A

Cut out Dimensions

186mm X 9omm

Depth

120mm

Digital Input Level

Battery Voltage (Negative) except charging Alternator which is positive.


It is our endeavour to constantly upgrade our products, hence specifications are subject to change without any notice.

Download PDF File


MRM PROCOM PVT. LTD.

Contact Us

( *represents compulsory fields )

Tips on getting accurate quotes. Please include product name, order quantity, usage, special requests if any in your inquiry.



Contact Details
  • MRM PROCOM PVT. LTD.
  • Plot No. 20-21, Sector 59, Phase-2, Faridabad - 121004, Haryana, India
  • Send Inquiry      Call Me Free Offline Send SMS
  • Mr. Pankaj Gupta (Director)
MRM PROCOM PVT. LTD. All Rights Reserved.